Notification classes must be defined to enable Tracer ES to notify the intended recipients of building alarms in the most efficient manner possible. Tracer ES supports as many alarm notification classes as needed for each panel type.
Notes: To receive alarms from Tracker panels, the Tracer ES system must be configured in the building control panel as a recipient of alarms with the Tracker service tool. The workstation ID of the Tracer ES system must match the workstation ID used in the programming of the Tracker alarm event receiver for the Tracer ES system to receive Tracker alarms. See table below. To receive alarms from Tracker Version 12 or higher panels, Tracer ES will "register foreign" with the building control panel during the building discovery process.
Workstation number |
Workstation ID |
1 |
82 |
2 |
83 |
3 |
84 |
4 |
85 |
5 |
86 |
6 |
87 |
7 |
88 |
8 |
89 |
9 |
90 |
10 |
91 |
To map alarm priority levels to notification classes: